Iron, out of the BlueBox circuit.
TAVILGironaDS-i65 · DN652025

- Iron · μg/L
- 1.148 → <50Iron · μg/L
- Langelier index
- +0,20 → 0,00Langelier index
- Hardness · mg/L CaCO₃
- 80 → 79Hardness · mg/L CaCO₃
Problem
The first check on the closed BlueBox circuit showed a high iron load: 1,148 μg/L, against under 50 μg/L in the make-up water. The Langelier index was +0.20, consistent with a slight scaling tendency.
Action
Technical survey of the circuit and installation of a DS-i65 on DN65, 316L stainless steel body. Physical treatment: no cartridges, no consumables and no chemical dosing in the unit. Two analytical checks, on 27/02/2025 and 07/04/2025.
Result
In 39 days iron falls from 1,148 μg/L to under 50 μg/L and the Langelier index returns to 0.00. Circuit hardness holds almost unchanged, from 80 to 79 mg/L CaCO₃: the water is not demineralised.